Danger! Electric shock can kill!
- Before working on the pump, disconnect from the power supply and secure against reconnection.
- Check that no voltage is present.
Danger! Pressurised system!
- Before working on the motor or pump connections, close the shut-off valves.
Warning! Risk of scalding due to hot water!
- Avoid direct contact with escaping hot water.
- The pump housing can similarly reach a high temperature due to the hot medium being pumped.
- Whenever the motor is opened up, replace the seal in the pump housing.

For maintenance, first close the isolation valves.

Demount M6-screws completely.

Remove pump motor.

Carefully lift the rotor off the bearing pin.

Using a limescale remover, free the rotor and separating cap of limescale. If necessary, replace the rotor. Use only soft, non-metallic tools (e.g. brush, cloth, toothpick).



Reposition the rotor on the bearing pin.

Dispose of used O-ring.

Insert new O-ring into the pump housing and press slightly into place.

Remount pump motor.

Tighten M6-screws
(max. 5 Nm).

Slowly open the shut-off valves again.

To vent any remaining air, switch the pump on and off several times …

… and open the DHW tap several times …

… until the pump runs quietly.